AIN5A analog inputs module

Analog Input module, auto addressed with 5 onboard integrated Analog Inputs.

Technical Details

  • 5 onboard integrated Analog Inputs
  • RS485 Interface
  • Supply Voltage: 9-14 V
  • Typ: 20mA @ 12V
  • max: 30mA @ 12V

Input Specifications:

  • Voltage : 0 – [(V+) + 0.6V]

Additional Specifications :

  • CPU: STM32F100 Arm Cortex-M3 core
  • 2 orange LEDs (Power, Comm.)
  • 3 green LEDs (Diagnostics AI.1 – AI.3)
  • 1 green LED (Diagnostics AI.4 – AI.5)

Housing :

  • Dimensions (WxHxD): 36 x 90 x 58 mm
  • Material: Plastic
  • Mounting: on standard mounting DIN rail EN 60715 TH35
  • Protection Class:
  • Connection : removable spring terminals
  • Mounting position : Optional

Description :

AIN5A is a 5 Inputs module, designed to support the majority of the

commonly used sensors of the market. Either for active or passive

sensors, it can measure resistance up to 800 kΩ, offering solutions for

high demanding installations. The connection of each sensor to the

modules input is taken place per pair, also the (-) and the (+), where

the (-) is common to the GND. All sensors independent of the type, must

be connected in pair, in order to have a common GND.

Currently sensors  supported :

Active : 0-5V, 0-10V, 2-10V, 1.5-5.5V

Passive : PT100, PT500, PT1000, Ni100, Ni1000, NTC1.8k, NTC10k, NTC20k, KTY81-210, PTC10k, LM2352

What we do

We specialize in programmable automation controllers with on board programmable on Python language. An easy way to create automations for HVAC, plumbing and electrical needs.

On Board Programmable

The entire project is based upon an RTOS, so that concurrent multitasking is supported for the micro-python algorithms…

Graphical User Interface

A user-friendly, short and yet powerful graphical interface guides the programmer and the user to hand the controller fast…

Structured Programming

The storage, which user can use is up to 55 MB for both micro-python algorithms and data…

Python Code Programmed

During code writing, a list of all global variables provided by all routines, are appearing on the left and can be easily downloaded and used in the code…

Graphic Editor

Actually, there are no limits on the capabilities of designing and organizing a completed, good-looking graphic presentation…

Auto IO Addressing

The mapping can be expanded by adding a new IO module, or downsized by unmounts an IO module. The mapping can be also canceled if needed…